Alaam Global

Generator Range

Six power tiers from 10 to 100 kVA. Every unit ships with a soundproof canopy and built-in bulk fuel tank — ready for commercial and industrial deployment across the Middle East and Africa.

Entry LoadUnit 1 of 9

10 kVA

8 kW continuous output

≤ 72 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Yanmar L100V
Alternator
Stamford UCI224E
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
2.8 L/hr at 75% load
Autonomy
357 hrs at 75% load
Noise Level
≤ 72 dB(A) at 7m
Dimensions
1,600 × 750 × 1,050 mm
Weight
480 kg
Engine Brand
Yanmar
Typical Applications
Small offices
Retail units
Telecom shelters
Light workshops
Light CommercialUnit 2 of 9

20 kVA

16 kW continuous output

≤ 72 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Yanmar 4TNV88
Alternator
Stamford UCI224F
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
4.5 L/hr at 75% load
Autonomy
222 hrs at 75% load
Noise Level
≤ 72 dB(A) at 7m
Dimensions
1,900 × 800 × 1,150 mm
Weight
620 kg
Engine Brand
Yanmar
Typical Applications
Restaurants
Small hotels
Medical clinics
Construction sites
Mid CommercialUnit 3 of 9

30 kVA

24 kW continuous output

≤ 73 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Yanmar 4TNV98
Alternator
Stamford UCI274C
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
6.2 L/hr at 75% load
Autonomy
161 hrs at 75% load
Noise Level
≤ 73 dB(A) at 7m
Dimensions
2,100 × 850 × 1,200 mm
Weight
780 kg
Engine Brand
Yanmar
Typical Applications
Mid-size offices
Supermarkets
Schools
Light manufacturing
Mid CommercialUnit 4 of 9

30 kVA

24 kW continuous output

≤ 73 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Volvo Eicher E483
Alternator
Stamford UCI274C
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
6.4 L/hr at 75% load
Autonomy
156 hrs at 75% load
Noise Level
≤ 73 dB(A) at 7m
Dimensions
2,150 × 860 × 1,210 mm
Weight
810 kg
Engine Brand
Volvo Eicher
Typical Applications
Mid-size offices
Supermarkets
Schools
Light manufacturing
Heavy CommercialUnit 5 of 9

45 kVA

36 kW continuous output

≤ 74 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Volvo Eicher E494
Alternator
Stamford UCI274D
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
9.1 L/hr at 75% load
Autonomy
109 hrs at 75% load
Noise Level
≤ 74 dB(A) at 7m
Dimensions
2,400 × 950 × 1,300 mm
Weight
1,050 kg
Engine Brand
Volvo Eicher
Typical Applications
Hotels
Hospitals
Data centres
Large retail
IndustrialUnit 6 of 9

60 kVA

48 kW continuous output

≤ 74 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Yanmar 4TNV106T
Alternator
Stamford UCI274E
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
11.8 L/hr at 75% load
Autonomy
84 hrs at 75% load
Noise Level
≤ 74 dB(A) at 7m
Dimensions
2,650 × 980 × 1,380 mm
Weight
1,280 kg
Engine Brand
Yanmar
Typical Applications
Industrial plants
Mining sites
Large hospitals
Telecom towers
IndustrialUnit 7 of 9

60 kVA

48 kW continuous output

≤ 75 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Volvo Eicher E494T
Alternator
Stamford UCI274E
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
12.0 L/hr at 75% load
Autonomy
83 hrs at 75% load
Noise Level
≤ 75 dB(A) at 7m
Dimensions
2,700 × 1,000 × 1,400 mm
Weight
1,320 kg
Engine Brand
Volvo Eicher
Typical Applications
Industrial plants
Mining sites
Large hospitals
Telecom towers
Heavy IndustrialUnit 8 of 9

100 kVA

80 kW continuous output

≤ 75 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Volvo Eicher E4H4
Alternator
Stamford HCI444D
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
19.5 L/hr at 75% load
Autonomy
51 hrs at 75% load
Noise Level
≤ 75 dB(A) at 7m
Dimensions
3,200 × 1,100 × 1,600 mm
Weight
1,980 kg
Engine Brand
Volvo Eicher
Typical Applications
Heavy industry
Oil & gas
Large data centres
Campus power
Prime PowerUnit 9 of 9

160 kVA

128 kW continuous output

≤ 76 dB(A) at 7m
1,000 L tank
415V / 3-Phase
Engine
Volvo Eicher E4H6
Alternator
Stamford HCI444F
Fuel Tank
1,000 L
Canopy
Soundproof
Voltage
415V / 3-Phase
Frequency
50 Hz
Fuel Consumption
30.5 L/hr at 75% load
Autonomy
32 hrs at 75% load
Noise Level
≤ 76 dB(A) at 7m
Dimensions
3,600 × 1,200 × 1,750 mm
Weight
2,650 kg
Engine Brand
Volvo Eicher
Typical Applications
Large industrial plants
Oil & gas facilities
Campus power
Data centres

Need a Custom Specification?

Our team can advise on load sizing, fuel planning, and site installation across the MEA region.